How to make a ThermexWeld connection:

1

COMBOWELD
STARTER KIT

2

CLEAN CONDUCTORS
WITH WIRE BRUSH.
FREE OF OIL & MOISTURE
3

ITEMS READY FOR
USE. REFER TO USER
INSTRUCTION BOOKLET
4

SELECT NUMBER OF FIBRE
SEALS REQUIRED FOR
JOINT TO BE MADE
5

PLACE FIRST FIBRE
SEAL AND
CONDUCTORS
6

PLACE SECOND
FIBRE SEAL
7

COMPRESS FIBRE SEALS
USING CLAMP MECHANISM
8

PLACE DISC, FULL
WELD METAL, STATER
AND STARTER POWDER.
CLOSE CAP.
9

MOVE ALL FLAMMABLE
PRODUCTS 1m AWAY.
LIGHT WITH A:
-FLINT IGNITER OR
-SPARK IGNITER
10

OPEN MOULD, REMOVE WELD
DISCARD USED SEALS


CU-TECH
WELDED JOINTS

GENERAL:
Cu-Tech ThermexWELD moulds, weld metals and tools are designed to work as a system and are not necessarily compatible with other manufacturers items.

Observe all local Safety Regulations.

The exothermic reaction results in HOT items, caution must be taken at all times.

Contact LECTRO-TECH for:
TRAINING MATERIAL INSPECTORS GUIDE
OR ANY ASSISTANCE


 
- Top of page -

LECTRO-TECH (Pty) Limited | Tel:+27 (0)11 786-4818 | Fax:+27 (0)11 786-4819 | Email: info@lectro-tech.co.za
 